Skip to content Skip to navigation menu
click to open Expanded view

Eaton - Surge filter - 100A - 3PH - 80kA - Enclosed - PPF1003CEI

  • Eaton
  • BW#: 01130827
  • Mfr#: PPF1003CEI
  • UNSPSC#: 39101600
Login or Register to view price
QTY

Features
  • The Eaton PPFi is designed to provide point-of-entry (Category C) & sub-circuit protection (Category B) against power surges caused by external sources such as lightning strikes & substation switching as well as providing a measure of protection from surge events generated on the secondary side of the filter
  • The Eaton PPFi is a 3-stage protection system utilizing primary & secondary MOV protection in conjunction with a low-Q LC filter
  • The unit provides filtering of the line harmonics, noise & RF transmitters with a cut-off frequency of <10Hz & a minimum attenuation of 70dB above 1MHz
  • Special care has been taken in the design of the filter to minimize ringing caused by light loads, surge diverter operation & inductive load back-EMF


  • Applications
  • An ideal device for all category locations


  • Specifications

  • Dimensions (H x W x D, mm): 800 x 600 x 200
  • Weight (kg): 50
  • Warranty: 5 years

  • Electrical:
  • Input voltage: 380 - 440VAC 3 Phase
  • Max Continuous Voltage (Mcov): 300VAC L-N
  • Temporary overvoltage - TOV: 320VAC, 15 mins
  • Test classification: Class II
  • Primary protection L-N: CEi: 1,200J/ph, 3,600J total. DEi: 1,800J/ph, 5400J total. EEi: 3,600J/ph, 10,8000J total
  • Secondary protection L-N: CEi: 600J/ph, 1,600J total. DEi: 600J/ph, 1,800J total. EEi: 600J/ph, 1,800J total
  • Common mode protection N-E:CEi: 2,130J. DEi: 710J. EEi: 710J
  • Aggregate rating: CEi: 7,530J. DEi: 7,910J.. EEi: 13,310J
  • Current rating continuous (standard models): 100A
  • Recommended maximum over current protection: 100A
  • Residual current: <1 mA
  • Short circuit withstand (1 sec): 29kA
  • Protection modes: Line-Neutral, Neutral-Earth
  • In 8/20us (Line-Neutral) Nominal Surge Life: CEi: 30kA x 20 hits/ph; DEi: 45kA x 20 hits/ph; EEI: 90kA x 20 hits/ph
  • In 8/20us (Neutral-Earth) Nominal Surge Life: 45kA x 20 hits
  • Ismax 8/20us (Line-Neutral) Max surge level: CEi: 80kA; DEi: 120kA; EEI: 240kA
  • Ismax 8/20us (Neutral-Earth) Max surge level: CEi: 120kA; DEi: 40kA; EEI: 40kA
  • Filter attenuation: 70dB nominal above 1MHz
  • Initial clamp voltage (Line-Neutral): 560V (350Vac RMS)
  • Initial clamp voltage (Line-Earth): 1240V (700Vac RMS)
  • Initial clamp voltage (Neutral-Earth): 680V (420Vac RMS)
  • Residual voltage (Vpl) Line-Neutral: <900Vac (3kA, 8/20uS) IEC61643.1
  • Residual voltage (Vpl) Line-Earth: <1100Vac (3kA, 8/20uS) IEC61643.1
  • Residual voltage (Vpl) Neutral-Earth: <1000Vac (3kA, 8/20uS) IEC61643.1
  • Internal protection (fusing): All surge diverter connections are fused via HRC fuses to IEC269-2-1
  • Terminations: Bolted lug. 8mm bolts for phase & neutral connections
  • 8mm PE (earth) stud provided on geartray

  • Communications:
  • Alarms/indicators: Mimic panel display via LED (2 colour), OK - Green; Protection Fault - Red. Dry contact alarm relay output 250Vac/32Vdc, 10A, 4kV isolation, Alarm under-voltage cutoff 180Vac

  • Environmental & Standards:
  • Enclosure rating: IP24
  • Design standards: IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D AS1768-2007 Cat B,C,D,E AS3000, AS3100, CE mark
  • Environment: -10 to 65C, 10 to 90%RH (non-condensing)
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications