Skip to content Skip to navigation menu
click to open Expanded view

Terasaki - Ar Acb Body Size Ar2 1250A 3P 65Ka W/Ocr21Cl Sht/Mtr 240V Ac - ARB2123MSTD

  • TERASAKI
  • BW#: 00837271
  • Mfr#: ARB2123MSTD
  • UNSPSC#: 39121616
Login or Register to view price
QTY

Features
 • Super fast clearance of short circuits, minimises the thermal and mechanical stress on busbars during an electrical fault
 • Unique 'Double Break' contact mechanism provides excellent mechanical and electrical endurance reducing life cycle costs
 • High short time withstand rating (I) providing superior selectivity and ensuring a reliable power supply
 • Isolating clusters on body, allow complete ACB circuit to be replaced and maintained without shutting down the switchboard
 • On-board energy management monitoring which facilitates energy usage reporting
 • Standards Compliance: JIS C 8372 EN 60947-2 NEMA SG3 IEC 60947-2 ANSI C37.13

Specifications

 • Component Type ACB: Body
 • Altitude, Operating (No Derating): 2000
 • Latching Current: 65
 • Icm, Rated Short-Circuit Making Capacity, 440V AC: 143
 • Icm, Rated Short-Circuit Making Capacity, 690V AC: 105
 • Making Capacity, Peak, 440V AC: 143
 • Making Capacity, Peak, 690V AC: 105
 • In, Rated Current at 40°C: 1250
 • Ics, Rated Service Short-Circuit Breaking Capacity, AC (IEC 60947): 50
 • Icw, short time withstand current, 1s (rms): 65
 • Icw, short time withstand current, 3s (rms): 50
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 440V AC: 65
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 690V AC: 50
 • Depth: 385
 • Rated Frequency: 50 / 60 Hz
 • Height: 460
 • Relative Humidity, Max: 85
 • Relative humidity, min: 45
 • IP Rating: IP41
 • Number of Poles: 3
 • Electrical Service Life Without Maintenance, 460V AC: 12000
 • Electrical Service Life Without Maintenance, 690V AC: 10000
 • Mechanical Service Life With Maintenance: 30000
 • Mechanical Service Life Without Maintenance: 15000
 • Shock Acceleration (Max.): 20
 • Operating Temperature, Max: 40
 • Operating Temperature, Min: -5
 • Total Breaking Time: 30
 • Total Making Time: 80
 • Vibration Acceleration (Max.): 0.7
 • Uimp, Impulse Withstand Voltage: 12
 • Ui, Rated Insulation Voltage: 1000
 • Un, Nominal Operational Voltage, AC: 690
 • Weight: 45
 • Width: 354
 • Automatic Spring Discharge Device: Yes
 • Control Circuit Safety Shutter: Yes
 • Ground Fault Trip Characteristic: Yes
 • Instantaneous Time Delay Trip Characteristic: Yes
 • Lockable Button Covers: Yes
 • Long Time Delay Trip Characteristic: Yes
 • Main Circuit Safety Shutter: Yes
 • Position Padlock: Yes
 • Sealable OCR Cover: Yes
 • Short Time Delay Trip Characteristic: Yes
 • Withdrawable: Yes

Minimum sell quantity:

Order Quantity Multiple:

Technical Specifications

Number of Pole 3
Height 460 mm
Width 354 mm
Weight 45 kg
Rated Insulation Voltage 1000 V (rms)