Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric Vigirex 56173 Residual Current Protection Relay - RH99M - Din Rail Mounting - 30mA To 30A - 220/240V AC - 50/60Hz

  • Schneider Electric
  • BW#: 02412189
  • Mfr#: 56173
  • UNSPSC#: 39121601
Login or Register to view price
QTY

Features
  • Protection: when detecting significant leakage current in the line it monitors, the relay trips the breaker at the top end of it, through its shunt trip auxiliary
  • Monitoring: signalling leakage current by LED, bargraph or digital display on front, and by an output dry contact. Available in single-line and multi-line variants monitoring up to 12 different distribution lines.
  • Residual current sensitivity ranging from 30 mA to 30 A, fixed or adjustable, for A type relays,
    and 30 mA to 3 A for B type relays
  • Trip time delay ranging from 0 to 4.5 seconds, fixed or adjustable
    o Networks with operating voltage up to 1000 V, and frequency up to 400 Hz
    o lines with current carrying capacity up to 3200 A
    o main switchboards (at the foot of the transformer) in most demanding industrial environments (overvoltage withstand category IV)
  • Type A or type B as per IEC 60 755
  • Compliant with standards:
    o IEC 60 755 and IEC 60947-2 appendix M (certificates by Kema laboratories available)
    o UL 1053 listed, CSA C22.2 N° 144 for North-America
    o EAC for Russia, CCC for China
  • DIN profile, to clip on rail or secure on backplate
  • 72x72mm, for switchboard front plate or door mounting, using clips
    o Closed toroids; for new installations (new switchboards or extensions), with cable capacity up to 630 A for A type relays, 250 A for B type relays
    o Rectangular sensors; for lines with capacity up to 3200 A (busbars, or cables above 630 A)
    o Split toroids; to equip distribution lines already in operation, with cable capacity up to 250 A


  • Applications
  • Electrical networks operating with voltage above 500 V (up to 1000) or frequency higher than 60 Hz (up to 400)
  • Distribution lines with capacity 630 A and above (up to 3200)
  • Upgrade of switchboards already in operation
  • Monitoring and protection at the root of power distribution
  • Three-phase supplied loads including rectifiers : lifts, cranes, HVAC, high-power speed drives, UPS...
  • Single-phase DC boost power supply in some electric vehicle chargers
  • Loads including single-phase speed drives: washing machines, air-conditioning units, heat pumps, food processors)
  • power supply network equipped with harmonic filters


  • Specifications

  • [Us] rated supply voltage : 220...240 V AC 50/60 Hz
  • 220...240 V AC 400 Hz
  • Power consumption in VA : 4 VA
  • Minimum sell quantity:

    Order Quantity Multiple:

    Catalogue Page Number: 17-71

    Technical Specifications

    Type Residual Current Protection Relay
    Terminal Connection Auxiliary Power Supply: Terminal Block Cable(S) 0.2-2.5 Mm² Flexible Awg 24...Awg 12
    Auxiliary Power Supply: Terminal Block Cable(S) 0.2-2.5 Mm² Rigid Awg 24...Awg 12
    Auxiliary Power Supply: Terminal Block Cable(S) 0.25-2.5 Mm² Flexible Awg 24...Awg 12
    Fault: Screw Terminal Cable(S) 0.2-2.5 Mm² Flexible Awg 24...Awg 12
    Fault: Screw Terminal Cable(S) 0.2-4 Mm² Rigid Awg 24...Awg 12
    Width 90 mm
    Height 85 mm
    Length 76 mm
    Weight 276 g
    Rated Impulse Withstand Volt 8 Kv
    Mounting Mode DIN rail
    Air Temperature for Storage -55-85 °C
    Air Temperature for Operation -35-70 °C
    Alternate Products